Dear Moritz,
this error occurs if you use  in a wall a very thin or a very thick layer.
Such configurations might cause problems with the transferfunctions.
 
If you have a very thin Layer like you have with: PVCBEL = 2 mm you should model this as an masless Layer.
 
A hint:
The position of the error in the *.inf gives you the wall whichs causes the error.
Then I normaly delete layer by layer to see which Layer causes the problem.
 

your TRNSYS Hotline Team

T.Welfonder, M.Rudolph


Mailto:Hotline@transsolar.com; http://www.transsolar.com
--------------------------------------------------------------------------------------------------------------------
NEW: TRNFLOW - Integrated airflow model into TYPE 56
       
If you want more information about TRNFLOW
please send a mail  to hotline@transsolar.com
--------------------------------------------------------------------------------------------------------------------
TRNFLOW COURSE
Date:  not fixed jet (November 2003)
Price: Euro 650.- + VAT

If you are interested in the next TRNFLOW COURSE
please send a mail  to hotline@transsolar.com
--------------------------------------------------------------------------------------------------------------------
TRNSYS KURS

Seminar 1       Einführung in die Arbeit mit TRNSYS
                Grundlagen der dynamischen Simulation.
                Systemgenerierung mit IISiBat (z.B. solare Brauchwasseranlage).
                Gebühr  Euro 900.- zzgl. USt. pro Person
                Termin  Do.-Fr. 10./11. November 2003

Seminar 2       Gebäudesimulation mit TRNSYS
                Eingabe der Gebäudedaten mit PREBID. Modellierung der
                Heiz-,Kühl- und Regelungstechnik mit IISiBat und Bewertung
                der Ergebnisse anhand aktueller Beispiele.
                Gebühr  Euro 900.- zzgl. USt. pro Person
                Termin  Do.-Fr. 27./28.November 2003





 
 
 
-----Ursprüngliche Nachricht-----
Von: Moritz Köpcke [mailto:moritz.koepcke@sonnenwaerme-ag.de]
Gesendet: Montag, 18. August 2003 20:14
An: TRNSYS Mailing List
Betreff: Active Layer

Dear TRNSYS users,
 
please give me somebody a hint, what could be meant by: "UNABLE TO FIND A ROOT AFTER INDICATION THAT A ROOT EXISTED". That is an error message generated by PREBID during the transfer function coefficients calculation, because of my active layer. I believe I designed it properly (cold ceiling modules), but after quite a while, I still cannot find the problem:
 
WALL KMODUL2
 LAYERS   = ALUMINIUM KLAYER ALUMINIUM LDECKE BET150 STWOLL012 ESTRICH45 PVCBEL
 THICKNESS= 0.036     0      0.005     0      0.15   0.05      0.045     0.002 
 ABS-FRONT= 0.6   : ABS-BACK= 0.6 
 HFRONT   = 11 : HBACK= 11
 
whereas
LAYER KLAYER
 PSPACING=   0.12 : PDIAMETER=   0.01 : PWALLTHICKNESS=  0.001 : PCONDUCTIVITY= 1382.4 : CPFLUID= 4.18
and
LAYER LDECKE
 RESISTANCE=     1.25
 
I also tried different time bases. And another short question: How is it defined, that the modules hang below the ceiling and do not lay on the floor or are even vertical boundaries?
Thank you very much!
Moritz