Gopu,
This error simply means that you have assigned the same logical unit
number to more than one external file. Most often, logical unit numbers are
assigned as parameters - you can check through each Type that contains an
external file reference and make sure that all logical unit parameters are
unique. You should also make sure that all your logical unit numbers are
above 10. The numbers below 10 are reserved in TRNSYS for things like the
list file, the keyboard, etc.
Cheers,
David
At 05:36 AM 4/24/2002 -0700, you wrote:
>Hello Trnsys users!,
>
> any body encoutered an error like
>-----------------------------------------------
>***** ERROR ***** TRNSYS ERROR # 71
> LOGICAL UNIT FOR ASSIGN STATEMENT HAS BEEN PREVIOUSLY
>ASSIGNED
> *|? Which file contains the transfer function
>iformation (*.TRN)? |1000
>
>--------------------------------------------
>
>
>
> i am using a external weather file, and 3 other
>external data files for TYPE56 bulding model and the
>file type are like *.BLD,*.TRN and *.DAT file. the
>problem is in the DCK file the logical number is
>assigned two times by the IISibat.,but even if i
>modify the DCK file and ASSIGN 4 different LOGICAL
>numbers for different files,.. when i RUN the program
>in IISibat,using the F8 function or run Icon in the
>toolbar, it is re-writing the DCK file before
>executing that filee....so how i can I avoide such an
>error
>
>mvh
>
>
>=====
>gopu sridhar
>student in solar Engineering (Energy)
>Högskolan Dalarna
>Solar Energy Research Center SERC
>Dept. of Energy, Environment and Construction
>S-78188 Borlänge
>phone:+46-073-7144741
>
>__________________________________________________
>Do You Yahoo!?
>Yahoo! Games - play chess, backgammon, pool and more
>http://games.yahoo.com/
*********************************************************************************
Thermal Energy System Specialists (TESS)
David BRADLEY 2916 Marketplace Drive - Suite 104
Project Engineer Madison, WI 53719
Phone: (608) 274-2577 USA
Fax: (608) 278-1475
E-mail: bradley@tess-inc.com
Web Page: www.tess-inc.com
"Providing software solutions for today's energy engineering projects"
****************************************************************************
*****